5.

Technical specifications

General product data
Product class
General
Rated Voltage
Rated apparent power
Rated active power
Hard parallel
configuration
Performance
Efficiency
Dynamic output
performance
Architecture
Table 5.1: HiPerGuard MV UPS general data
5.1.

Utility input

Input
Voltage tolerance
Rated frequency
Frequency tolerance
Displacement power factor
at supply
Battery charging current
Power Distribution system
Current distortion THDi
Table 5.2: HiPerGuard MV UPS input specifications
HI PE RG UA RD M V UP S U S E R M A N UA L
7.2 kV IEC
12kV IEC
6-6.6kV
10-11 kV
Up to 10 units
98% for 50% to 100% loading
96% for 25% to 50% loading
In line with IEC62040-3 VI SS 111
ZISC enabled line interactive
±10 %
50 Hz/60 Hz
± 2 %
> 0.96
0-50%
IT, 3-Wire Input
< 3%
15 kV ANSI
12.47-13.8kV
2500 kVA
2500 kW
From nominal voltage
From rated frequency
Under nominal conditions
Grid supplied on top of the load power.
Two setpoints, grid and generator
(default is 10% for both)
Please contact ABB for other
distribution systems
Full linear load, under nominal
conditions, operating on power
conditioning mode
TE C H NI C A L S PE C I FI CAT IO NS
24kV IEC
20-22kV
Single unit
Load power
factor 1.0
Under
nominal
conditions
44/103