Table 8.6: MV UPS Emergency Power Off steps
8.7.

Hard fault

Hard faults are extremely rare situations where multiple failures occur at the same time, and the system
is not capable of holding the voltage any longer.
In the case of hard-parallel configuration, the remaining units will support the load (N+1 configuration,
for instance). If the load power exceeds the remaining units overload capability, the system will be
commuted to bypass mode.
8.7.1.
During Power Conditioning mode
Step
User Action
1
System encounters a hard fault, which
prevents it from normal operation
2
3
4
Table 8.7: System reaction to fault while in PCM
1. Closing the bypass applies for single unit configuration where no unit redundancy is achieved
8.7.2.
During Independent mode
Step
User Action
1
System encounters a hard fault, which
prevents it from normal operation
2
HI PE RG UA RD M V UP S U S E R M A N UA L
System Response
Open all DC breakers at the DC energy source
if configured to do so
System Response
MV UPS output voltage synchronizes with
utility voltage magnitude, frequency and
phase, while simultaneously commands S
1
to close
When S
is closed, S
and S
abp
in
commanded to open
After S
and S
are opened, MV UPS stops
in
out
the PEBBs and reverts to bypass mode
System Response
Commands to close S
abp
with input voltage then simultaneously
synchronizes load voltage with mains voltage
frequency, phase and magnitude. Otherwise,
MV UPS waits in the previous state until S
closes
O P E R AT I O N
abp
are
out
. If MV UPS is locked
abp
99/103