ABB HiPerGuard MV UPS User Manual page 78

Medium voltage ups
Hide thumbs Also See for HiPerGuard MV UPS:
Table of Contents

Advertisement

ID
Event
W5.211
Demand Response Power Controller
communications link invalid
W5.213 Demand Response Power Controller
limiting charging
W5.215 Energy Storage communications link
not valid
W5.221 PEBB Group AC imbalance high
W5.228 Test Mode without switchgear enabled Test Mode has been requested without MV
W5.230 Input current imbalance high
W5.231 Output current imbalance high
Table 7.3: List of Warnings and description
7.1.6.2.
List of Faults
ID
Event
F5.23
DC bus voltage too high
F5.26
DC bus voltage too low
F5.31
Energy Storage strings insufficient
F5.47
System DC volts measurement error
F5.52
PE120 DC volts measurement invalid
F5.84
PS to MB Comms Low
F5.85
UC to ML 0 link failure
HI PE RG UA RD M V UP S U S E R M A N UA L
Description
There is a communication problem between the
Demand Response Power Controller and the MV
UPS.
The Demand Response Controller is LIMITING STATE
OF CHARGE of the Energy Storage.
There is a communication problem between the
Energy Storage and the MV UPS.
An imbalance of utility or load is causing excess 2nd
harmonic ripple.
Switchgear being enabled.
High level of current imbalance has been detected
on the input grid.
High level of current imbalance has been detected
on the UPS output.
Description
The average DC bus voltage has been detected as
too high. The system has TRIPPED and the load has
been transferred to BYPASS.
The averaged DC Bus voltage has fallen to a level
where storage is deemed to be depleted.
The system has TRIPPED and the load has been
transferred to BYPASS.
The expected number of energy storage strings are
not available to allow the system to continue
running. The system has TRIPPED, and the load has
been transferred to BYPASS.
There is a discrepancy between the various DC
voltage measurements in DC bus and in PCS-120
modules.
By comparison of Energy Storage Bus voltage and
DC Bus voltage measurements in each inverter
module, it has been determined one or more of
these measurements is invalid.
The Master Controller CPU has indicated a
communications handshake failure.
The CPU in the DLL IO block has indicated a failure
in communications handshake between UC and ML
link 0.
U S E R I NT E R FA CE
78/103