ABB HiPerGuard MV UPS User Manual page 51

Medium voltage ups
Hide thumbs Also See for HiPerGuard MV UPS:
Table of Contents

Advertisement

6.4.2.
External auxiliary 3-phase power supply input
An external power supply is required for system start-up. This is not needed once the system is running.
The requirements are summarized in Table 6.1. The connection terminals are located in the APS
enclosure on fuse holders F6-1, F6-3, and F6-5.
External AC supply
Supply
Required supply current
Maximum prospective short-circuit current
Input voltage
Voltage tolerance
Table 6.1: External AC supply requirements
6.4.3.
Digital outputs
Five changeover relays are provided in the MV UPS, for status and alarm signaling. Each relay has a
voltage-free changeover contact, which is wired to terminals X10-1 to X10-15 inside the APS enclosure.
Digital Outputs
Switching capacity
Terminal
X10-1
X10-2
X10-3
X10-4
X10-5
X10-6
X10-7
X10-8
X10-9
X10-10
X10-11
X10-12
HI PE RG UA RD M V UP S U S E R M A N UA L
Rated voltage
30 Vdc
240 Vac
Signal
Warning
Fault
Run
Independent mode
EX TE R NA L P OW E R A ND CO N T RO L CO N NE C T IO NS
3-phase, 3-wire, 50/60 Hz, TN
10 A
22 kA
380-480 Vac
±10%
Steady state current
5A
Default setting
Description
Warning status. Relay contacts
shown as when machine has a
warning
Fault status. Relay contacts
shown as when machine has a
warning
Running status. Relay contacts
shown as when machine is
operating
Operating status. Relay contacts
shown as when MV is operating
in Independent mode
51/103