3 2 Connection

3 2 1
05 Output
If the UPS is connected via the power cord, use a
connection
proper socket (grounded and shockproof) and
diagram of 3kVA S
pay attention to the capacity of the socket.
The UPS system has an input breaker on the
standard cabinet.
3 2 2
The output sockets and types of the UPS are
shown below.

Table 5: UPS model output sockets

Model No
PowerValue 11T G2 1 kVA B
PowerValue 11T G2 1 kVA S
PowerValue 11T G2 2 kVA B
PowerValue 11T G2 2 kVA S
PowerValue 11T G2 3 kVA B
PowerValue 11T G2 3 kVA S
For PowerValue 11T G2 3kVA S model, connect the
output and ground wires to the terminal block
according to Figure 5 and Table 6 shown below.
05

UPS input connection

UPS output connection

Output Socket -IEC(pcs)
4*C13
3*C13
4*C13
6*C13
4*C13+1*C19
3*C13+Terminal block
Table 6: Connecting output and ground
wires to terminal block
Terminal
Terminal
Wire function
wire size
position
rating
L
Line Out
1.5mm
N
2.5mm
Neutral Out
(14AWG-
Output
12AWG)
Ground
3 2 3

External batteries connection

When connecting the external batteries modules
(EBM), it is recommended to use the EBM that
matches the corresponding UPS model.

Table 7: EBM and corresponding UPS model connections

UPS Model
EBM model
PowerValue 11T G2 1 kVA B
External battery 11T G2 1 kVA
PowerValue 11T G2 1 kVA S
External battery 11T G2 1 kVA
PowerValue 11T G2 2 kVA B
External battery 11T G2 2 kVA
PowerValue 11T G2 2 kVA S
External battery 11T G2 2 kVA
PowerValue 11T G2 3 kVA B
External battery 11T G2 3 kVA
PowerValue 11T G2 3 kVA S
External battery 11T G2 3 kVA
CONNECTING THE WRONG EBM WILL
CAUSE ABNORMALITY OR PERMANENT
DAMAGE.
A STANDARD TYPE BATTERY CONNECTOR
WARNING
ON THE REAR PANEL IS USED FOR
CONNECTING THE BATTERY PACK.
IN CASE OF INSTALLING A CUSTOMIZED
EXTERNAL BATTERY PACKAGE, IT IS VERY
IMPORTANT TO FOLLOW THE NEXT STEPS
TO AVOID THE RISK OF ELECTRICAL SHOCK.
DANGER
1. Prepare the battery cable and connector able
to withstand the needed current.
2. Install a proper DC breaker between the UPS
and the external batteries.
3. If there is a battery breaker, turn it off first.
Then connect the battery cable to the EBM
connector on the rear of the UPS.
4. Connect the input power cord of the UPS to
mains power supply. The battery will start to
charge.
Tightening
torque
2
2
0.5Nm
(4.4 Lb In)