Overspeed protection system
Table of Contents

Advertisement

Operating Manual
MHM-97442
Figure 5-27: Example signal form with trigger thresholds and limit values for sensor
type PR 6423
Signal range: -2 to -18 V
Distance sensor - tooth: approximately 0.90 - 1.0 mm (sensor PR 6423)
Adjusted to approximately -5.5 V over tooth
A. Upper sensor voltage limit
B. Linear measuring range: lower limit
C. Upper gap limit
D. Sensor adjustment range
E. Lower gap limit
F. Upper trigger threshold (UTT)
G. Lower trigger threshold (LTT)
H. Linear measuring range: upper limit
I. Maximum output amplitude of an eddy current measuring chain
J. Lower sensor voltage limit
K. Signal maximum = tooth
L. Signal minimum = tooth gap
These parameters are grayed out if VR or Hall has been selected for parameter Sensortyp.
Basic Settings
Enter here the basic setting for the measurement.
MHM-97442, Rev. 2.06
Configuration
February 2023
99