Define with limit value Value 1 and limit value Value 2 a limit window. The function output
is set when the speed value of this channel is within the window. See
Figure 5-45: Diagram limit monitoring Inside window
A. Alarm activated
B. No alarm
C. Value 2
D. Value 1
E. Hysteresis
The function output is in initial state (no alarm) as long as the measuring value is outside
the limits by considering the hysteresis values.
Temperature warning 55°C
The output is switched, when the temperature, measured with the internal temperature
sensor, exceeds +55°C for more than 60 seconds.
Temperature warning 65°C
The output is switched, when the temperature, measured with the internal temperature,
sensor exceeds 65°C for more than 60 seconds.
Trip limit value
This function behaves exactly like the trip function (see
>= Acceleration limit value
The characteristic of the switch is increasing. The condition for the output is met when the
acceleration reaches the defined limit value Value 1.
If the acceleration falls below the limit value minus hysteresis again, the alarm output is
reset. Enter the hysteresis in input field Hysteresis.
<= Acceleration limit value
The characteristic of the switch is decreasing. The condition for the output is met when
the acceleration falls below the defined limit value Value 1.
116
Operating Manual
MHM-97442
Figure 5-45
Trip limit
value).
MHM-97442, Rev. 2.06