Emerson Machinery Health AMS 6300 SIS Operating Manual page 95

Overspeed protection system
Table of Contents

Advertisement

Operating Manual
MHM-97442
Enter here the KKS/RDS-PP number according to the power plant identification system
under which sensor or measuring chain are documented in the project documentation.
This designation is stored in the monitor and serves as identification. The maximum length
for the KKS/RDS_PP text is 20 characters.
Group Plant
Plant
Enter here the designation for the factory where the monitoring system is installed. The
maximum length for the text is 40 characters.
Block
Enter here the designation for the turbine stage where the monitoring system is installed.
The maximum length for the text is 40 characters.
Sensor Input
Configure here the connected sensor. All details of this tab regarding levels and trigger
thresholds are related to the original input signal. The sensor signal socket Sens. on the
front plate of the monitor provides the absolute value of the original input signal of the
connected sensor (Hall effect sensor or eddy current measuring chain) attenuated by
factor 0.15. There is no signal at this socket if a VR sensor is connected.
Figure 5-25: Sensor Input
Group General
Sensor type
Select the connected sensor type form this list field. Depending on the selection, different
limit input fields of group Measured quantities are enabled. The following sensor types
are available:
Eddy-Current
Choose Eddy-Current if an eddy current sensor is connected.
MHM-97442, Rev. 2.06
Configuration
February 2023
95