Emerson Machinery Health AMS 6300 SIS Operating Manual page 30

Overspeed protection system
Table of Contents

Advertisement

Installation and commissioning
February 2023
Table 4-3: Pin assignment A6381
Terminal
16
17
18
19
20
21
22
23
24
25
A6371/00 Backplane 'Trip Voted'
Connect the outputs of the relay logic to the backplane terminal strip. The connection of
the supply voltage for the overspeed protection system is also made through these
terminal strip. See
Figure 4-6: Terminal strip A6371/00
Table 4-4: Pin assignment A6371/00
Terminal
1
2
3
4
5
6
7
8
9
30
(continued)
Designation
GND(Inp)
Enable
Prf2
U-
Out1
Out3
Out5
PulsOut-X-C
PulsOut-Y-C
PulsOut-Z-C
Not used
Not used
Figure 4-6
and
Table 4-4
Designation
UB+
U-
UN+
U-
R 2oo3 Trip 1
NO 2oo3 Trip 1
R 2oo3 Trip 2
NO 2oo3 Trip 2
R 2oo3 Out2
Ground binary inputs
Input Enable Test value
Input Test value 2 activation
Ground Digital outputs
Digital- / Function output 1
Digital- / Function output 3
Digital- / Function output 5
Collector Pulse output 1
Collector Pulse output 2
Collector Pulse output 3
Supply voltage + (redundant)
Supply voltage (redundant)
Supply voltage + (redundant)
Supply voltage (redundant)
Changeover contact Trip Relay 1
Make contact Trip Relay 1
Changeover contact Trip Relay 2
Make contact Trip Relay 2
Changeover contact Relay Out 2
Operating Manual
MHM-97442
MHM-97442, Rev. 2.06