Emerson Machinery Health AMS 6300 SIS Operating Manual page 152

Overspeed protection system
Table of Contents

Advertisement

Functions and applications
February 2023
2. Where appropriate, unplug the PROFIBUS cable.
3. Unscrew the mounting screws, unplug the configuration cable and remove the
4. Set the jumper for the RS 485 interface of the new monitor in accordance to the
5. Move the new monitor into the slot and press it firmly but gently into the
6. Load the configuration into the new monitor.
7. Enter bus address and baud rate according to your notes (Monitor → Set
8. Remove the interface cable after successful configuration and entering of bus
9. Where appropriate, reconnect the PROFIBUS cable.
Postrequisites
If, because of a defect, there is no possibility to read out the configuration from the
monitor, load either the configuration from an available file, from another monitor, or
create a new configuration (see Configuration, Initialize).
152
Do not close AMS 6300 Configuration.
monitor from the slot.
jumper settings of the old monitor.
connector. Fasten the screws at the front plate to secure the monitor in the slot.
a) Connect the monitor through the USB interface to the PC / Laptop.
b) If the monitor is switched on, the software automatically connects to the
monitor.
c) At a new monitor without any configuration the dialog for initialization of
new monitors automatically opens. If the dialog does not open
automatically, click Monitor → Configuration → Initialize.
d) Select with the configuration of another monitor, the related list field is
enabled. Select the corresponding configuration from the list. Alternatively,
select with a saved configuration for loading a saved configuration file. Click
OK to confirm and close the dialog.
e) Click
or Monitor → Configuration → Send to send the configuration
into the new monitor.
communication parameter).
address and baud rate.
After changing the address for the PROFIBUS communication, power off and power
on the monitor again to enable the address change. This can be done, for example,
by pulling out and plugging in of the monitor.
Operating Manual
MHM-97442
MHM-97442, Rev. 2.06

Advertisement

Table of Contents
loading

Table of Contents