3. Click Monitor → Set monitor keyword to open the New monitor Keyword dialog.
4. Enter the received keyword for the reset in field Old monitor keyword and define a
5. Click OK to confirm the change and to close the dialog.
Set communication parameter (only RS 485 and PROFIBUS
communication)
Select Set communication parameter to open the Communication parameters dialog
(see
Figure
RS 485 interface. The monitor address applies also for the PROFIBUS communication.
Note
To enable the address change for the PROFIBUS communication, power the respective
monitor off and on again. This can be done, for example, by pulling out and plugging in
the monitor. It is not necessary to restart the monitor if the address is only used for
communication through the RS 485 interface.
Parameter Monitor baud rate:
Parameter Monitor address:
The settings that appear after the opening of the dialog are currently stored in the
monitor. Click OK to store the changes of the parameters in the monitor.
Figure 5-17: Dialog Communication parameters
Configuration
This menu contains configuration related commands.
Receive
Click Receive to read the configuration parameters from the connected monitor.
Send
88
new keyword for the monitor (fields New monitor keyword and Confirm new
monitor keyword).
The new keyword must consists of at least 6 and not more than 20 characters.
5-17). Define here baud rate and address for the communication through the
Select between 38400, 57600, and 115200 baud. The baud
rate must be identical at all devices connected to one bus
line.
Set an address in the range of 1 to 255. Each device
connected to the same bus must have a unique address. Two
devices on the same bus with the same address will lead to
communication problems.