Emerson Machinery Health AMS 6300 SIS Operating Manual page 37

Overspeed protection system
Table of Contents

Advertisement

Operating Manual
MHM-97442
Figure 4-12: Connection example with PR 9376 Hall effect sensor
A. Hall effect sensor PR 9376
B. Terminal box
C. Cable LIYCY-CY 2x2x0.25mm
D. 9-pole sub-D terminal block monitor A, B, and C (analog signals)
E. Cabinet
F. Load resistors for Channel OK detection
G. Cabinet ground
H. Protective ground
VR sensor (variable reluctance sensor)
Cable recommendation
To achieve undisturbed and proper measurements even with longer cables, Emerson
recommends using cables of type LiYCY-CY 2x2x0.25mm
AMS 6300 SIS. At distances greater than approximately 400 m between terminal box and
AMS 6300 SIS, cables with bigger crosssections are recommended.
connection and an example for shielding and grounding of the cables.
These kind of sensor types generally do not require a voltage supply.
MHM-97442, Rev. 2.06
Installation and commissioning
2
(maximum 400 m)
2
between terminal box and
February 2023
Figure 4-13
shows the
37