Configuration
February 2023
Figure 5-28: Basic Settings
Group Measuring functions
Safety function (Trip)
Define here the safety function of the system. When the condition for the selected safety
function is met, the trip will be released. The trip signal is routed to the relay logic on the
backplane. Choose from the following functions:
Speed
•
As soon as the trip limit value, defined in tab Digital outputs is reached, the trip for the
monitor is released.
Direction of rotation
•
When the detected rotational direction is opposite to the normal rotational direction,
the trip for the monitor is released.
•
Speed + Direction
When the conditions for at least one of the two safety functions are met, the trip for
the monitor is released.
Note
The safety functions Direction of rotation and Speed + Direction can not be selected if VR
(variable reluctance sensor) has been selected for parameter Sensor Input → Sensor type.
The detection of rotational direction is not possible with variable reluctance sensors.
Mode of measurement
Define here the measuring mode. The selected measuring mode influences the
measurement time. Choose from the following measuring modes:
100
Operating Manual
MHM-97442
MHM-97442, Rev. 2.06