MHM-97442
Figure 5-35: Trigger Wheel with chamfered flanks - symmetry 10%
A. Tooth width < Gap width (B-A)
B. Tooth width + Gap width
Figure 5-36: Trigger Wheel with chamfered flanks - symmetry 30%
A. Gap width < Tooth width (B-A)
B. Tooth width + Gap width
Standstill detection
Enter here the time for the Standstill detection. It defines how many seconds must elapse
before standstill is indicated after the last pulse is detected at the signal input. The
configured standstill time must be longer than the time between two measured pulses
with the running machine. Message Standstill is reset as soon as the next pulse is detected
at the signal input. See
Note
This parameter does not define the standstill time of function Standstill on Digital
Outputs.
Backplane type
Select here the type of backplane used for the system.
Voted
Not-Voted
Ensure that this setting corresponds to the installed backplane (A6371 Trip Voted or
A6371/10 Trip Not Voted). If the wrong type is entered here, the system indicates Relay
error and switches off Channel OK.
MHM-97442, Rev. 2.06
Standstill indication
for further information.