Appendix A
Table 10-1 Advanced Grid Support Functions: Parameter Values and Range of Adjustability.
Grid Support
Function /
Parameter Label
Funct. Abbr.
PV_CURVE_V1
PV_CURVE_P1
PV_CURVE_V2
PV_CURVE_P2_GEN
PV_CURVE_P2_LOAD
PV_OLRT
Overvoltage
Trip / OV
OV2_TRIP_V
OV2_TRIP_T
OV1_TRIP_V
OV1_TRIP_T
Undervoltage
Trip / UV
UV1_TRIP_V
UV1_TRIP_T
UV2_TRIP_V
UV2_TRIP_T
Overfrequency
/ OF
OF2_TRIP_F
OF2_TRIP_T
OF1_TRIP_F
OF1_TRIP_T
Underfrequenc
y / UF
UF1_TRIP_F
UF1_TRIP_T
UF2_TRIP_F
UF2_TRIP_T
Frequency-
Droop / P(f)
PF_DBOF
PF_DBUF
PF_KOF
PF_KUF
PF_OLRT
* Setting based on apparent power rating of 7600 VA.
** Setting based on 100% reactive power capability of 5700 VAr.
*** There is a max delay of 95 ms ± 10 ms to compensate for hardware mechanical response.
68
Parameter
Default /
Parameter
Inverter
Range
Setting
1.06
1.05 – 1.09
1.00
N/A
1.10
1.07 – 1.10
N/A
N/A
0
0 – 1.0
10.0
0.5 – 60.0
1.20
1.20
0.16 / 50 ms***
0.16
1.10
1.10 – 1.20
13.0
1.0 – 13.0
0.88
0 – 0.88
21.0
21.0 – 50.0
0.5
0 – 0.50
2.0
2.0 – 21.0
62.0
61.8 – 66.0
0.16 / 50 ms***
0.16 – 1000.0
61.2
61.0 – 66.0
300.0
180.0 – 1000.0
58.5
50.0 – 59.0
300
180.0 – 1000.0
56.5
50.0 – 57.0
0.16 / 50 ms***
0.16 – 1000.0
0.036
0.017 – 1.0
0.036
0.017 – 1.0
0.05
0.02 – 0.07
0.05
0.02 – 0.07
5
0.2 – 10.0
Installation and Owner's Manual for Generac PWRCell Inverter
Units
Comments
V p.u.
Per-unit nominal voltage.
W p.u.
Per-unit rated active power output.
V p.u.
Per-unit nominal voltage.
Applicable only if inverter can only generate active
W p.u.
power and not absorb power.
W p.u.
Per-unit rated active power absorption.
s
Open Loop Response Time in seconds.
Per Unit voltage based on Nameplate Nominal
V p.u.
Voltage.
s
Clearing time in seconds.
Per Unit voltage based on Nameplate Nominal
V p.u.
Voltage.
s
Clearing time in seconds.
Per Unit voltage based on Nameplate Nominal
V p.u.
Voltage.
s
Clearing time in seconds.
Per Unit voltage based on Nameplate Nominal
V p.u.
Voltage.
s
Clearing time in seconds.
Hz
s
Clearing time in seconds.
Hz
s
Clearing time in seconds.
Hz
s
Clearing time in seconds.
Hz
s
Clearing time in seconds.
Hz
Single-sided deadband value.
Hz
Single-sided deadband value.
Per-unit frequency change corresponding to 1 per-
N/A
unit power output change.
Per-unit frequency change corresponding to 1 per-
N/A
unit power output change.
s
Open Loop Response Time in seconds.
Need help?