Introduction ...Inside Front Cover Read This Manual Thoroughly ...IFC Contents ...IFC Operation and Maintenance ...IFC How to Obtain Service ...IFC Authorized Dealer Locator Number ...IFC Safety Rules ...2 Standards Index ...3 Section 1 – General Information ...4 Unpacking/Inspection ...4 Protection Systems ...4 NEC Requirement for Arc Fault Circuit Interruption Breaker for Bedrooms ...4 The Generator ...5...
IMPORTANT SAFETY INSTRUCTIONS Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators SAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safe operation be copied and posted near the unit’s installation site. Safety should be stressed to all operators and potential operators of this equipment.
ELECTRICAL HAZARDS • All generators covered by this manual produce dangerous electrical voltages and can cause fatal electrical shock. Utility power delivers extremely high and dangerous voltages to the transfer switch as does the standby generator when it is in opera- tion.
Section 1 — General Information Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators DANGER Only qualified electricians or contractors should attempt such installations, which must comply strictly with applicable codes, standards and regulations. UNPACKING/INSPECTION After unpacking, carefully inspect the contents for damage.
SYSTEM SET LED The “System Set” LED is lit when all of the following conditions are true: 1. The AUTO/OFF/MANUAL switch is set to the AUTO position. 2. The utility voltage being supplied to the unit is being sensed by the PCB. If the utility sense volt- age is not connected to the unit or if it is below 168 volts AC, then the system set light will flash rapidly.
Section 1 — General Information Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators NOTE: The natural gas adjustment screw is preset during installation and should not need any further adjustment. 1.9.2 12KW AND 15KW, 990CC ENGINES To reconfigure the fuel system from NG to LP , follow these steps: NOTE: The primary regulator for the propane supply is...
• Install the transfer switch indoors on a firm, stur- dy supporting structure. • To prevent switch distortion, level the switch if nec- essary. This can be done by placing washers between the switch enclosure and mounting sur- face. • Never install the switch where water or any corro- sive substance might drip onto the enclosure.
Section 2 — Post Installation Start-up and Adjustments Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators Do not open or mutilate the battery. Released electrolyte has been known to be harmful to the skin and eyes, and to be toxic. The electrolyte is a dilute sulfuric acid that is harmful to the skin and eyes.
7. When certain that utility supply voltage is com- patible with transfer switch and load circuit rat- ings, turn OFF the utility power supply to the transfer switch. 8. On the generator panel, set the AUTO/OFF/ MANUAL switch to MANUAL. The engine should crank and start.
Section 2 — Post Installation Start-up and Adjustments Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators 5. Turn ON the utility power supply to the transfer switch, using the means provided (such as a util- ity main line circuit breaker). 6.
If this procedure or the equipment are not available, locate the nearest Generac Guardian Dealer and they can perform the adjustments. NOTE: A service fee may be charged for this adjustment. ENGINE GOVERNOR ADJUSTMENT If both AC frequency and voltage are correspondingly high or low, adjust the engine governor as follows: 2.7.1 7 KW UNITS...
Section 3 — Operation Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators NOTE: The access panel on top of the control panel must be removed to adjust the voltage regulator. NOTE: The voltage regulator is housed above the genera- tor's control panel.
3. Set the generator’s AUTO/OFF/MANUAL switch to AUTO. 4. Set the generator’s main circuit breaker to its ON (or closed) position. With the preceding steps complete, the generator will start automatically when utility source voltage drops below a preset level. After the unit starts, loads are transferred to the standby power source.
Section 3 — Operation Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators 3.5.2 TRANSFER BACK TO UTILITY POWER SOURCE When utility power has been restored, transfer back to that source and shut down the generator. This can be accomplished as follows: 1.
NOTE: If the fault is not repaired, the overcrank feature will continue to activate. 3.7.3.1 Approximate Crank Cycle Times • 15 seconds ON • 7 seconds OFF • 7 seconds ON • 7 seconds OFF • Repeat for 45 seconds Approximately 90 seconds total 3.7.4 OVERSPEED...
Section 4 — Maintenance Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators CHANGING THE ENGINE OIL 4.3.1 ENGINE OIL RECOMMENDATIONS Use oil of American Petroleum Institute (API) Service Class SG, SH or SJ. Use all season SAE 5W-30 Synthetic oil.
Figure 4.7 — 12 kW and 15 kW Engine Air Cleaner Screw SPARK PLUG(S) Reset the spark plug(s) gap or replace the spark plug(s) as necessary. See Section 4.13 for mainte- nance requirements. 1. Clean the area around the base of the spark plug(s) to keep dirt and debris out of the engine.
Section 4 — Maintenance Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators Lead-acid batteries present a risk of fire because they generate hydrogen gas. The following procedures are to be followed: • DO NOT SMOKE when near the battery; •...
The exhaust from this product gets extremely hot and remains hot after shutdown. High grass, weeds, brush, leaves, etc. must remain clear of the exhaust. Such materials may ignite and burn from the heat of the exhaust system. The maximum ambient temperature for the generator is 40°...
Section 4 — Maintenance Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators 4.13 SERVICE SCHEDULE ATTENTION: It is recommended that all service work be performed by the nearest Generac/Guardian Authorized Dealer. SYSTEM/COMPONENT X = Action R = Replace as Necessary * = Notify Dealer if Repair is Needed.
TROUBLESHOOTING GUIDE PROBLEM The engine will not crank. The engine cranks but will not start. The engine starts hard and runs rough. The Auto/Off/Manual switch is set to OFF , but the engine continues to run. There is no AC output from the generator.
Section 7 — Exploded Views and Parts Lists Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators Enclosure – Drawing No. 0D3416-R PRE PACKAGED UNITS ONLY 44 85 79 80 32 Generac ® Power Systems, Inc. 49 49...
Page 35
ITEM PART NO. QTY. DESCRIPTION 0C6140 ASSEMBLY, ENCLOSURE BASE 0D1901 ASSEMBLY, ENCLOSURE BASE (7KW) 0C6735 SUPPORT, ROOF FOLDING 0C7061 ENCLOSURE, FRONT 0C7062 ENCLOSURE, EXHAUST SIDE 0C7062A ENCLOSURE, EXHAUST SIDE (7KW) 0C7063 ENCLOSURE, SIDE & BACK 0C7063A ENCLOSURE, SIDE & BACK (7KW) 0C7064 ENCLOSURE, ROOF 0C7065...
Page 36
Section 7 — Exploded Views and Parts Lists Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators Control Panel – Drawing No. 0E7974 34 Generac ® Power Systems, Inc.
Page 37
ITEM PART NO. QTY. DESCRIPTION 0E7886A CIRCUIT BREAKER 30A X 2P 240V (7KW) 0E7886C CIRCUIT BREAKER 40A X 2P 240V (8.5KW) 0E7886E CIRCUIT BREAKER 50A X 2P 240V (12KW) 0E7886F CIRCUIT BREAKER 60A X 2P 240V (13KW) 0E7886G CIRCUIT BREAKER 70A X 2P 240V (15KW) 0A1801 ASSEMBLY, BATTERY CHARGER ENGINE...
Page 38
Section 7 — Exploded Views and Parts Lists Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators 7 kW GTS Load Center Assembly – Drawing No. 0E7975 36 Generac ® Power Systems, Inc.
Section 10 – Warranty Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators NOTE: This Emission Control Warranty Statement pertains to this product only IF the generator size is 15 kW or below. CALIFORNIA EMISSION CONTROL WARRANTY STATEMENT YOUR WARRANTY RIGHTS AND OBLIGATIONS The California Air Resources Board (CARB) and Generac Power Systems, Inc.
Emission Control System Warranty (ECS Warranty) for 1995 and later model year engines: (a) Applicability: This warranty shall apply to 1995 and later model year engines. The ECS Warranty Period shall begin on the date the new engine or equipment is purchased by/delivered to its original, end-use purchaser/owner and shall con- tinue for 24 consecutive months thereafter.
Section 10 – Warranty Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators GENERAC POWER SYSTEMS STANDARD "TWO YEAR" LIMITED WARRANTY FOR GUARDIAN “EMERGENCY AUTOMATIC STANDBY GENERATORS” For a period of two years from the date of original sale, Generac Power Systems, Inc. (Generac) will, at its option, repair or replace any part which, upon examination, inspection and testing by Generac or a Generac Authorized Warranty Service Dealer, is found to be defective under normal use and service, in accordance with the warranty schedule set forth below.