PWRcell 2P Inv.
Disable
Mod. Settings
Calibrate CTs
RCPn: 000100073212
< EXIT
SCROLL > NEXT • SELECT
Figure 7-17. PV + Storage - Partial Home (1 of 2)
TargMinImprtP
Enalslanding
NumTranSwtchs
ExTransVolt
Cancel
Figure 7-18. PV + Storage - Partial Home (2 of 2)
PV + Battery w / a PWRcell ATS and Load
Management for Managed Whole Home Backup
– System mode should be Self Supply, Clean
Backup, or Priority Backup.
– See
Figure
7-19,
Inverter "Mod. Settings:"
o 'EnaIslanding' should be 'on.'
o 'NumTranSwtchs' should be '1.'
o'EnaLoadShed' should be '1' for PWRman-
ager and / or SMMs only and '2' for PWR-
cell ATS Controller (with or without
SMMs).
o All other settings should be at their default
values.
TargMinImprtP
EnaIslanding
NumTranSwtchs
ExTransVolt
Cancel
Figure 7-19. PV + Storage - Whole Home (1 of 3)
Installation and Owner's Manual for Generac PWRCell Inverter
Menu
013436
0
on
0
95
Save
013434
Figure
7-20, and
Figure
0
on
1
95
Save
EnaIslanding
NumTranSwtchs
ExtTransVolt
ExportOverride
Cancel
Figure 7-20. PV + Storage - Whole Home (2 of 3)
CTTurnsRatio
EnaLoadShed
GridParInvrtrs
ACPVPower
Cancel
Figure 7-21. PV + Storage - Whole Home (3 of 3)
NOTE: Contact the Independent Authorized Service
Dealer (IASD) who installed the system if unsure of how
to proceed with any of the actions above.