Overload Behavior - Generac Power Systems PWRcelP XVT076A03 Installation And Owner's Manual

Table of Contents

Advertisement

Troubleshooting

Overload Behavior

Island Overload Event
Overload on Voltage
(vulnerable when battery has
low SoC)
Overload on Current
(vulnerable to this condition
when system does not have an
external ATS)
62
Table 9-2. Overload Behavior
Cause
Load demand is too high and
the inverter has dropped it's
voltage in an attempt to
compensate.
There is too much load on the
protected loads panel.
Behavior
– If inverter output voltage drops below 114
V, inverter will attempt to shed any loads
connected to load management devices by
dropping frequency.
– If the inverter drops below 96 V for more
than 6 sec (loads will brown out during this
time), the system will blackout all loads.
– If inverter experiences current greater than
35 amps L-N, the inverter will prevent
transfer back to the grid and system will stay
islanded.
– If inverter experiences current greater than
35 amps for more than 15 seconds it will
blackout and attempt to power loads at an
increasing interval, starting at 20 seconds
and increasing by 20 seconds between each
attempt, up to a maximum of one hour.
Installation and Owner's Manual for Generac PWRCell Inverter
Solution
– Reduce house load
– Reduce house load