4.3.4 Recommended bus and cable lengths

Note
If components of different manufacturers are used in one network, there
might be diverging indications. The following information is based on the
specifications of Echelon
tions.
Dependent on the selected topology, the maximum transmission distances
achievable are different.

4.3.4.1 Bus shaped wiring

For a bus shaped wiring with a bus termination on both ends, the following
cable lengths are permissible:
(Bus termination on both ends: 105 Ω +/- 1%)
Cable type
Belden 85102
Belden 8471
Level IV, 22AWG
JY (St) Y 2x2x0,8
Tab. 4-2: Bus lengths with FTT-10 transceivers/bus topology, with terminations on both ends
When using a physical repeater, max. 5400 m can be reached.

4.3.4.2 Free Wiring

With a free wiring (tree, star) with a bus termination at one end, the following
cable lengths are permissible:
(Bus termination on one end: 52 Ω +/- 1%)
Cable type
Belden 5102
Belden 8471
UL Level IV, 22AWG
JY(St)Y 2x2x0,8
Tab. 4-3: Bus lengths with FTT-10 transceivers/Free wiring (tree, star), with termination on
one end
For a safe transmission in bus segments with a tree topology the following
points are to be observed:
1.
If there are different signal paths, e.g. in a ring-shaped topology, the longer transmission
path has to be taken into account.
2.
The maximum cable length is the total of all network conductors connected in the bus
segment.
®
and are to be understood merely as recommenda-
Bus length if only FTT-10 is used in a
segment
≤ 2700 m
≤ 2700 m
≤ 1400 m
≤ 900 m
Distance of two nodes
≤ 500 m
≤ 400 m
≤ 400 m
≤ 320 m
Bus length if FTT-10 and LPT-
10 are used in a segment
≤ 2200 m
≤ 2200 m
≤ 1150 m
≤ 750 m
Overall cable length with
10, 5 and 2.5 MHz clock
≤ 500 m
≤ 500 m
≤ 500 m
≤ 500 m
1.25 MHz clock
≤ 400 m
≤ 400 m
≤ 400 m
≤ 400 m
®
L
W
ON
ORKS