WAGO LONWORKS 750-319 Manual page 32

Modular i/o system
Table of Contents

Advertisement

32 •
The WAGO-I/O-SYSTEM 750
Power Supply
Recommendation
With the WAGO ProServe® Software smartDESIGNER, the assembly of a
fieldbus node can be configured. The configuration can be tested via the inte-
grated accuracy check.
The maximum input current of the 24 V system supply is 500 mA. The exact
electrical consumption (I
Coupler/Controller
I(5 V)
750-613
I(5 V)
Input current I(24 V) =
Note
If the electrical consumption of the power supply point for the 24 V-system
supply exceeds 500 mA, then the cause may be an improperly aligned node
or a defect.
During the test, all outputs, in particular those of the relay modules, must be
active.
(24 V)
=
Sum of all the internal current consumption of the connected
total
bus modules
+ internal current consumption coupler/controller
=
Sum of all the internal current consumption of the connected
total
bus modules
5 V / 24 V * I(5 V)
η = 0.87 (at nominal load)
) can be determined with the following formulas:
/ η
total
®
L
W