3.4 System Clock Verification

If a fault is detected with the system clock then the aim of should be to get to a safe operating point, where system
can be controlled using a different known clock.
3.4.1 Power-Up
The system clock should be verified at power on or reset. It may be necessary to test the clock once the
system has been initialised and the full system clock frequency has been set and stabilised.
3.4.2
Periodic
Periodic testing of the system clock can be made at any time where the application has the time available.
This is because the reference clock is typically much slower that the system clock in order to increase the
accuracy of the clock measurement.
(i.e. System clock = 32 MHZ, Reference clock = 15 KHz)
R01AN0749EG0201 Rev.2.01
Mar 04, 2014
VDE Certified IEC60730/60335 Self Test Library
Page 30 of 50