General Description Of The Boiler - REMEHA Quinta 45 Technical Information

Table of Contents

Advertisement

1

GENERAL DESCRIPTION OF THE BOILER

The Remeha Quinta 45 and Quinta 65 are wall hung condensing boilers which may be
also installed free standing on a suitable frame (option). The one piece cast aluminium
heat exchanger and other major components are contained within a sealed air box.
This forms the main boiler casing with a removable front section for maintenance
purposes. All electrical and electronic controls are contained within the instrument
panel mounted behind the drop down lower front panel.
The combined flue gas outlet and combustion air inlet are mounted on the top of the
boiler with the flow, return, gas and condensate connections located at the bottom.
The boiler is suitable for room sealed or open flue applications and has been designed
for central heating and indirect hot water production at working pressures not
exceeding 4 bar. It must be installed on a fully pumped system and is suitable for use
on both sealed and open vented installations (minimum operating pressure of 0.3 bar).
The pre-mix, down firing gas burner (NG or LPG) with its gas/air ratio control system
ensures clean, trouble free operation with higher than average efficiencies of 110%
(NCV) in the condensing mode combined with ultra low NOx and minimum CO
emissions. The standard control package allows actual and set values to be read and
adjusted on the built in digital display which also provides normal operating and fault
code indication.
An intelligent, advanced boiler control 'abc' continuously monitors the boiler
conditions, varying the heat output to suit the system load. The control is able to react
to external "negative" influences in the rest of the system (flow rates, air / gas supply
problems) maintaining boiler output for as long as possible without resorting to a lock
out condition. At worst the boiler will reduce it's output and/or shut down (shut-off
mode) awaiting the "negative" conditions to return to normal before re-starting.
The 'abc' control cannot override the standard flame safety controls.
The boilers meet the requirements of the EC regulations and directives:
- 90/396EEC Gas appliances directive
- 92/42/EEC Efficiency directive
- 73/23/EEC Electrical low voltage directive
- 89/336/EEC E.M.C. directive
- 97/23/EEC Pressure equipment directive PED (art. 3, sub.3)
Remeha Quinta 45 - reference-number: PIN 0063BL3253
Remeha Quinta 65 - reference-number: PIN 0063BL3253