Shut-Down; Temporary Shut-Down With Frost Protection; Permanent Shut-Down Without Frost Protection - REMEHA Quinta 45 Technical Information

Table of Contents

Advertisement

17.4. Check the flame via the inspection window. The flame should be stable, mainly
blue with burner surface covered by orange dots.
17.5. Run the boiler at part-load by pressing the 'm'- and [-]-keys simultaneously.
17.6. When part-load speed is reached, check values against the table and adjust if
necessary using the Þ screw on the combi valve (see fig. 21).
17.7. Check the flame via the inspection window. The flame should be stable, with a
regular orange flame distribution.
17.8. Check the ionisation level, measurement in Volts between terminal 4 and earth,
minimum 4 A (1 V dc  1 A dc).
NOTE: The full load adjustment changes the gas/air graph slope angle, whilst the part
load adjustment shifts the base point on a parallel axis, each adjustment therefore
alters the previous setting slightly. Repeat the process 17.2 to 17.7 and re-check the
values as many times as necessary until they are correct at both loads.
18.
Remove the flue gas analyser. Seal the test point.
19.
Fit the boiler front panel.
20.
Allow boiler to run up to its set flow temperature and shut off.
21.
When pumps have stopped, vent the system and check the water pressure.
22.
The boiler is now ready for use.
23.
Check system controls.
24.
Set system controls to the required values.
NOTE: The Remeha Quinta 45 and 65 is supplied with a number of factory default
settings which should be correct for most installations. If other setting values are
required: see Par. 6.5 and 6.6.

9.2 Shut-down

9.2.1 Temporary shut-down with frost protection

- do not isolate the electric power supply.
- do not close the gas cock.
- use the switch function, see Par. 6.1.3.

9.2.2 Permanent shut-down without frost protection

- Set system controls to off.
- Isolate the electric power supply.
- Close the gas cock.
55979.indd 54
55979.indd 54
Quinta 45/65
54
Remeha
2-4-2009 9:42:41