3.3 General Specification

(to be read with above table)
- One piece cast aluminium heat exchanger
- 1" BSP (f) and 1¼" BSP (m) flow and return connections
- ¾" BSP (m) gas connection
- Maximum operating pressure of 4.0 bar
- Maximum operating temperature of 95°C
- Low NOx (max 21 ppm, O
- Pre-mix, fully modulating (18 -100%) gas burner with gas/air ratio control for
maximum efficiency
- Intelligent advanced boiler control 'abc' c/w a comprehensive operating, service and
fault diagnostic facility
- Available for conventional flue or room sealed operation
- Capable of remote BMS (0 -10V, On/off and High/low control options)
- Supplied fully factory assembled
- Powder coated enamel steel casing
- Suitable for use with a Natural gas or propane as standard (choices on
commissioning)
- Supplied as standard with safety interlock facility, temperature indication, control
and high limit sensors, common alarm and boiler run indication
- Efficiency of 99% at 80/60°C (H
- Max efficiency of 105% (H
- Manufactured to ISO 9001
- CE approved
Options
- Floor frame
- Two pipe flue/air inlet adapter plate (excentric room sealed)
- DHW-sensor
- Broag-Remeha weather compensating controllers
- Heat exchanger cleaning tool
- EMC filter for boiler sensor or boiler thermostat cables
55979.indd 12
55979.indd 12
= 0%, dry, according to DIN 4702, part 8)
2
)
i
) in fully condensing mode
i
12
Remeha
Quinta 45/65