Different Pressure Zones - REMEHA Quinta 45 Technical Information

Table of Contents

Advertisement

max eq. Length
eq. Length bend 45°
eq. Length bend 90°
Table 14 Calculation data room sealed applications
Example: Quinta 45, total length 10 m, 2 bends 90°.
80 mm: 10 m + 2 x 2 = 14 m < 16 m: flue OK.
Note: If the design parameters are outside the values shown in the above table or
there is any doubt over the flue system, please contact our technical department for
calculation to be undertaken.

7.3.6 Different pressure zones

Bird guard
Flue outlet
Air inlet
Fig. 09
Different pressure zones
04W4H7900004
55979.indd 37
55979.indd 37
Quinta 45
80/125 mm
m
16
m
m
37
Quinta 65
100/150 mm
13
1
2
2-4-2009 9:42:39
2-4-2009 9:42:39