Description
Flame
0)
simulation
Short circuit 24V Check wiring.
0!
No flame or no
0@
ionisation (after
5 start attemps)
Note:
Ionisation
measurement
in Volts
between
terminal 4 and
earth
(1V dc  1μA dc,
see Fig. 23)
0$
External
0%
influence
55979.indd 57
55979.indd 57
Cause/check points and remedy
- Gas valve shuts but burner surface continues to glow
due to incorrect combustion.
- Gas valve off but leaking on shut-down - burner flame
continuing.
No ignition spark, check:
- connection of ignition cable and spark plug cap
- ignition cable and electrode for insulation breakdown
- electrode gap; must be 3 - 4 mm
- earth continuity
Ignition spark, but no flame, check if:
- gas cock is open
- inlet gas pressure is sufficient
- gas pipe is vented (special attention for LPG use)
- gas valve is energised during ignition and also opens
- electrode is fitted properly, is clean and set
- the gas/air ratio is correct (see Par. 9.1)
- the gas pipe is not clogged or incorrectly sized
- the air supply and flue outlet is free of obstructions
- if the condensate siphon is clear
- there is no flue gas recirculation (internal/external)
Flame, but no or insufficient (<4μA) ionisation:
Visual check of flame:
- is flame core visible?
-
is flame geometry stable?
- check CO
at both part and full flame
2
- check ignition probe earthing
- check temperature sensors for loss current (humidty on
sensors)
- is analog control (0 - 10 V) volt free?
Visual check of ignition/ionisation probes:
- if white oxydes show, use sand paper or screwdriver for
cleansing
- check geometry and distance between both probes, i.e.
3 to 4 mm.
Voltage failure after lock out condition – original lock out
cause will not be displayed – check read out table for
additional fault code, ref. Par. 6.9
- power or control supply affected by external EMC
– check for EMC conformity