Setting Mode Service Level (X00) - REMEHA Quinta 45 Technical Information

Table of Contents

Advertisement

t-display
Second segment [y
0
1
2
3
Table 08 Boiler control option
* NOTE: Booster function n/a in UK

6.6 Setting mode service level (X00)

(only for the qualified service engineer)
To prevent accidental, unauthorised access by non-qualified persons the control
system requires an input code to gain access to the second level of boiler control.
- Press the 'm' - and 's'-keys simultaneously and hold. The 'code'-display now
shows a letter c with a random number in the t-display.
- While holding both keys pressed, set the t-display to 12, using the [+] or [-]-
keys and press the 'e'-key.
- The display will flash twice confirming acceptance of the access code.
- Release the keys and c12 will dissappear from the display. You are now in the
service mode
WARNING: changing factory defaults without reference to the tables contained in this
manual may result in incorrect operation.
- To delete the service code press the 'reset'-key once
- If no keys are pressed over a 15 minute period the service code will delete
automatically
Code
Description
Flow temperature set point
$
during forced part load
High limit temperature set point 90 - !0 (= 110°C)
%
Fan speed at full load (HTG)
^
55979.indd 25
55979.indd 25
Description
Operation mode
HTG and DHW off
HTG and DHW on
HTG on and DHW off
HTG off and DHW on
Setting range
20 - 90ºC
10- 60 hundreds
25
Preset
Q45
Q65
79
)0 (=100)*
52
2-4-2009 9:42:38
2-4-2009 9:42:38