- SR5240 - Optimising / weather-compensated boiler control for single boiler. These
controls are supplied with outside sensor and mounting kit for installation in the
boiler.
Communication between the Optimising / weather-compensated control and the
boiler control system is via an interface PCB supplied with the kit (to fit see fig. 17).
Connection via a two-core cable and plug supplied to plug K2 in the boiler.
Installation can also be made in a reference room. In this case, room compensation
can also be applied.
Connection via a two-core cable to terminals 1 and 2.
Set the x value of the boiler control operation parameter (A) to 1.
- 2945 C3 K - Optimising / weather-compensated boiler control for multiple boilers.
These controls are supplied with outside sensor, mounting and wiring kit for
installation in the boiler, see fig. 16.
Communication between the Optimising / weather-compensated control and the
boiler control system is via an interface PCB supplied with the kit (to fit see fig. 17).
Set the x value of the boiler control operation parameter (A) to 1.
Fig. 16
Fitting 2945 C3 K controller
pdf
1. rematic
control
®
2. Earth terminal
3. Terminal strip
4. rematic
adapter
®
5. Cable clamp
NOTE: Please refer to the relevant control leaflet for optimising / compensation settings.