Setting Mode Service Level (X00) - REMEHA Quinta 30 Technical Information

High-effi ciency condensing boiler
Table of Contents

Advertisement

Example: xy
11 - Boiler enabled internal modulation with booster on *
42 - Analog signal 0 -10V on temperature - HTG on and DHW off
23 - Boiler high/low - HTG off and DHW on
t -display
t
First segment x[
1
2
3
4
5
t -display
t
Second segment [y
0
1
2
3
Table 08
Boiler control option
* Note: Booster function n/a in UK

6.6 Setting mode service level (X00)

(only for the qualified service engineer)
To prevent accidental, unauthorised access by non-qualified persons the control
system requires an input code to gain access to the second level of boiler control.
- Press the 'm' - and 's'-keys simultaneously and hold. The 'code'-display now
shows a letter c with a random number in the t-display.
- While holding both keys pressed, set the t-display to 12, using the [+] or [-]-
keys and press the 'e'-key.
- The display will flash twice confirming acceptance of the access code.
- Release the keys and c12 will dissappear from the display. You are now in the
service mode
- HTG and DHW on (as default)
Description
Boiler control option
Boiler enabled internal modulation with booster on *
Boiler high/low
Boiler enabled internal modulation with booster off *
Analog signal 0-10V on temperature
Analog signal 0-10V on output %
Description
Operation mode
HTG and DHW off
HTG and DHW on
HTG on and DHW off
HTG off and DHW on
22
Remeha Quinta 30