Setting Mode Service Level ( ) - REMEHA Gas 110 Eco 115 Installation And Service Manual

Gas fired condensing boiler
Hide thumbs Also See for Gas 110 Eco 115:
Table of Contents

Advertisement

4.6 Setting mode service level (
(only for the qualified service engineer with product knowledge).
To prevent accidental, unauthorised access by non-qualified persons
the control system requires an input code to gain access to the
second level of boiler control.
- Press the
- and '
" "
"
code
-display now shows a letter
"
"
-display.
- While holding both keys pressed, set the
using the [+] or [-] - keys and press the
Code
Description
Flow temperature set point during forced
part load
High limit temperature set point
Fan speed at full load (HTG)
Fan speed at part load (HTG and DHW)
Modulation start point ∆T (F/R)
Interface selection (control option)
DHW cut-in ∆T
Fan speed at full load (DHW)
Intern
N/a
N/a
Forced part load time after start (HTG)
Fan speed at start
DHW control stop or boiler modulation set
point (based on parameter
DHW control option
Variable speed pump
HTG cut-in ∆T
N/a
Boiler type
Intern
Maximum delay time
Start point for 0 V analog signal
End point for 10 V analog signal
Intern
* NOTE:
See chapter 4.1.4 for values over two digits
26/01/2009 - 300014883-001-F
)
-keys simultaneously and hold. The
"
with a random number in the
-display to
-key.
"
"
Setting range
May not be changed!
May not be changed!
)
N/a
May not be changed!
May not be changed!
- The display will flash twice confirming acceptance of the access
code.
- Release the keys and
You are now in the service mode.
WARNING: changing factory defaults without reference to the tables
contained in this manual may result in incorrect operation.
- To delete the service code press the
,
- If no keys are pressed over a 15 minute period the service code will
delete automatically.
°C
-
-
(= 110 °C)
-
hundreds
-
hundreds
°C
-
internal (Modulating controls only)
external interface
-
read 1 - 5 °C
read 10 °C
read 15 °C
read 20 °C
-
hundreds
-
minutes
°C
-
= Three way valve (port A = HTG, port B = DHW)
= DHW pump
= inverted three way valve (port A = DHW, port B = HTG)
°C
(= -10 °C)-
-
minutes
°C
(= -50 °C)-
°C
-
(= 299)
Gas 110 Eco 115 / 65
will dissappear from the display.
reset
-key once
"
"
Preset
(= 100)*
(= 100)*
(= 103)*
(= 100)*
21