45
Where wire diameter used for the A.C. connection to or from the Battery Inverter
exceeds the maximum wire diameter for the plugs below (e.g. if a long cable run is
2
required and Voltage Rise Calculations require a wire of greater than 10mm
), use an
intermediary connection point close to the Battery to downsize the wire. Ensure that
the short-run wire type is appropriate for the current and temperature (e.g. 180°C
Silicone flex will carry much greater current than vs 90°C PVC) and use an intermediate
MCB at the intermediary connection point if required.
The steps for connecting the grid connector are as follows:
The steps for connecting the backup connector are as follows:
Note the smaller wire diameter on the backup plug.