Fig. 4.10.-1 Report Control Block
48
SPA/ Ethernet Adapter
Installation and Commissioning Manual
Buffered reporting needs mandatory Report Client definitions. Report Client
definitions links certain RCB to certain client. Client can import the CID file to
check what RCB instance it has to use. If Max property is defined to two,
configuration must have two clients with buffered reporting. In the list first defined
client uses first RCB instance (rcb name ...01) and second RCB uses second instance
(rcb name ...02 ). It is not mandatory to define clients in unbuffered reporting, but it
is recommended for clarity. Client IED Name has to match with the client name in
Substation Configuration description Language (SCL).
Every modification in RCB increases the rcb Configuration Revision property by
one. This integer value is also an exported CID file and the IEC 61850-8-1 client can
check between the received revision and file configuration revision.