ABB SPA-ZC 402 Installation And Commissioning Manual page 55

Spa/ ethernet adapter
Table of Contents

Advertisement

1MRS755380
SPA/ Ethernet Adapter
Installation and Commissioning Manual
Table 5.2.-1
Environmental test and conditions
Dry cold test
Damp heat test, cyclic
Table 5.2.-2
Electromagnetic compatibility tests
EMC immunity test level meets the requirements listed below
1 MHz burst disturbance test, class III
• Common mode
• Differential mode
Electrostatic discharge test, class III
• For contact discharge
• For air discharge
Radio frequency interference tests
• Conducted, common mode
• Radiated, amplitude-modulated
• Radiated, pulse-modulated
Fast transient disturbance tests
• All terminals
Surge immunity test
• Power supply, SPA-ZC402xxxA
• Power supply, SPA-ZC402xxxC
Power frequency (50 Hz) magnetic field
IEC 61000-4-8
Electromagnetic emission tests
• Conducted, RF-emission (Mains terminal)
Radiated RF-emission
CE approval
SPA-ZC 402
According to the IEC 60068-2-1
According to the IEC 60068-2-30
According to the IEC 60255-22-1
2.5 kV
1.0 kV
According to the IEC 61000-4-2 and IEC
60255-22-2
6 kV
8 kV
According to the IEC 61000-4-6 and
IEC 60255-22-6
10 V (rms), f=150 kHz...80 MHz
According to the IEC 61000-4-3 and
IEC 60255-22-3
10 V/m (rms), f=80...1000 MHz
According to the ENV 50204 and
IEC 60255-22-3
10 V/m, f=900 MHz
According to the IEC 60255-22-4 and
IEC 61000-4-4
4 kV
According to the IEC 60255-22-5 and
IEC 61000-4-5
4 kV, line-to-earth
2 kV, line-to-line
2 kV, line-to-earth
1 kV, line-to-line
300 A/m continuous
According to the EN 55011
EN 55011, class A, IEC 60255-25
EN 55011, class A, IEC 60255-25
Complies with the EMC directive
89/336/EEC and the LV directive
73/23/EEC
55