Settings; Limit Setting; Resetting The Protection Temperature Limiter (Stb) - JUMO KM-70 Operating Instructions Manual

Panel-mounting thermostat
Hide thumbs Also See for KM-70:
Table of Contents

Advertisement

5.1

Limit setting

( 1 ) Scale division
( 2 ) Limit pointer
( 3 ) Top stop
( 4 ) Limit arm
On limit ranges above 120°C, the limit that was set must be locked to prevent
re-adjustment.
5.2

Resetting the protection temperature limiter (STB)

After the temperature has dropped by about 10% of the scale span below the
set limit (critical temperature), the microswitch can be reset.
Adjust the switching point on the limit arm with a screwdriver before fitting
the thermostat in position.
Chapter 5.3 "Limit locking", page 20.
Press the reset button ( 1 ), until the microswitch is reset.