Floor Strength; Power; Grounding; Figure 5 Library's Ac Power Receptacle - Quantum ACL 4/52 Installation Manual

Automated tape library for dlt cartridges
Hide thumbs Also See for ACL 4/52:
Table of Contents

Advertisement

Chapter 1 Installation Requirements
Site Requirements
1

Floor Strength

1

Power

Figure 5 Library's AC
Power Receptacle
1

Grounding

The floor in the installation site must be a standard raised computer
floor rated at 250 lb/ft
Enterprise library.
The library's auto-ranging motor and logic power supplies accept
single-phase,
90–264 VAC input power at 47–63 Hz.
The power inlet connector is a IEC-320 connector. For international
applications you must replace the power cord set with a harmonized
3x2.0 mm
2
power cord set that is approved by the country where used.
Ground
Line
The installation site must provide an earth ground cable for the library.
ACL 4/52 Facilities Planning and Installation Guide
. This is sufficient to support a fully loaded
2
~100-120V / ~200 - 240V
4A / 2A
50/60 Hz
IEC-320 Type
Neutral

Advertisement

Table of Contents
loading

Table of Contents