Direct Access Parameter Information; Direct Access Parameters/Numbers - Toshiba vlp technology P9 ASD Installation & Operation Manual

Hide thumbs Also See for vlp technology P9 ASD:
Table of Contents

Advertisement

F000

Direct Access Parameter Information

The P9 ASD has the ability to allow the user direct access to the motor control functions. There are two
ways in which the motor control parameters may be accessed for modification from the EOI: Program 
Applicable Menu Path or Program  Direct Access  Applicable Parameter Number.Both methods
access the parameter via the Program mode. Parameters may also be accessed via communications. Once
accessed, the parameter may be viewed or changed.
The Program mode allows the user to develop an application-specific motor control profile. Motor
control functions may be set to accommodate specific power and timing requirements for a given
application. The configurable parameters of the Program mode that have user-accessible Parameter
Numbers are listed and described below.
Note: Parameter Settings are preceded by the number used to select an item if using
communications to write to a parameter location in memory (i.e., F000  0-Manual, 1- No
Trip on Acc/Dec, 2--No trip on Acc Only, etc.).
Note: Communications setting changes will require that the ASD input power be removed and then
re-applied for the changes to take affect.

Direct Access Parameters/Numbers

Automatic Acceleration/Deceleration
Program  Fundamental Accel/Decel 1 Settings
This parameter is used to enable acceleration and deceleration rates in
accordance with the applied load automatically.
The adjusted acceleration and deceleration times range from 12.5% to 800% of
the programmed values for Acceleration Time 1 (F009) and Deceleration
Time 1 (F010).
Settings:
0 — Manual
1 — Automatic ACC/DEC
2 — Automatic ACC Only
Note:
The motor and the load must be connected prior to selecting
Automatic Acceleration/Deceleration.
Automatic Torque Boost
Program  Fundamental Motor Set 1
This parameter allows the ASD to adjust the output torque in accordance with
the applied load automatically. When enabled Autotuning is performed — the
motor should be connected before performing an Autotune.
Settings:
0 — Disabled
1 — Automatic Torque Boost + Autotuning
2 — Sensorless Vector Control + Autotuning
P9 ASD Installation and Operation Manual
Direct Access Number — F000
Parameter Type — Selection List
Factory Default — Manual
Changeable During Run — No
Direct Access Number — F001
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — No
F001
81

Advertisement

Table of Contents
loading

Table of Contents