F574
Preset Speed 14 Operation Mode
Program Pattern Run Operation Mode
Same as Preset Speed 1 Operation Mode (
Preset Speed 15 Operation Mode
Program Pattern Run Operation Mode
Same as Preset Speed 1 Operation Mode (
Motor Overload Protection Level 1
Program Fundamental Motor Set 1
This parameter specifies the motor overload current level for Motor Set 1. This
value is entered as either a percentage of the full load rating of the ASD or as a
percentage of the FLA of the motor.
The unit of measurement for this parameter may be set to A/V (Amps) or it may
be set as a percentage of the ASD rating. The nameplated FLA of the motor
may be entered directly when Amps is selected as the unit of measurement
See
(
F701
to change the display unit).
Motor Overload Protection Level 1 settings will be displayed in Amps if the
EOI display units are set to A/V rather than %.
Stall Prevention Level
Program Protection Stall
This parameter specifies the output current level at which the output frequency
is reduced in an attempt to prevent a trip. The over-current level is entered as a
percentage of the maximum rating of the ASD.
Note:
The Motor Overload Protection parameter must enabled at
to use this feature.
Retain Trip Record at Power Down
Program Protection Trip Settings
This parameter Enables/Disables the Trip Record Retention setting. When
enabled, this feature logs the trip event and retains the trip information when the
system powers down. The trip information may be viewed from the (Program
 Utilities Trip History screen or the Monitor screen.
When disabled, the trip information will be cleared when the system powers
down.
Settings:
0 — Disabled
1 — Enabled
198
See
F561).
See
F561).
F017
Direct Access Number — F574
Parameter Type — Selection List
Factory Default — Forward Run
Changeable During Run — No
Direct Access Number — F575
Parameter Type — Selection List
Factory Default — Forward Run
Changeable During Run — No
Direct Access Number — F600
Parameter Type — Numerical
Factory Default — 100
Changeable During Run — Yes
Minimum — 10
Maximum — 100.0
Units — %
Direct Access Number — F601
Parameter Type — Numerical
Factory Default — (ASD-Dependent)
Changeable During Run — Yes
Minimum — 10
Maximum — 165
Units — %
Direct Access Number — F602
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
P9 ASD Installation and Operation Manual
F602