F854
Communications Option Speed Switch Monitor DeviceNet/
CC-Link
Program Communications Communication Settings
This parameter is used in the setup of the communications network by reading
the hardware-specific settings of the option card being used with the ASD.
If using the DEV002Z Devicenet card, this parameter reads the hardware
switch SW300 setting of the Devicenet card. SW300 sets the baud rate and the
MAC address of the option card that is connected to a node of the
communications system.
See the DeviceNet Option Instruction Manual (P/N 58683) for more
information on this parameter or see the Instruction manual for the option being
used with the P9 ASD.
Block Write Data 1
Program Communications Communication Settings
This parameter plays a role in the setup of the communications network by
establishing the type of data to be written to the ASD of the communications
link.
The communications network includes other ASDs and Host/Control computers
that monitor the status of the ASD(s), transfers commands, and loads or
modifies the parameter settings of the ASD.
Changes made to this parameter require that the power be cycled (off then on)
for the changes to take effect.
Settings:
0 — None
1 — FA00 (Command 1)
2 — FA20 (Command 2)
3 — FA01 (Frequency)
4 — FA50 (TB Output)
5 — FA51 (Analog Output)
Block Write Data 2
Program Communications Communication Settings
This parameter plays a role in the setup of the communications network by
establishing the type of data to be written to the ASD of the communications
link.
The communications network includes other ASDs and Host/Control computers
that monitor the status of the ASD(s), transfers commands, and loads or
modifies the parameter settings of the ASD.
Changes made to this parameter require that the power be cycled (off then on)
for the changes to take effect.
Settings:
0 — None
1 — FA00 (Command 1)
2 — FA20 (Command 2)
3 — FA01 (Frequency)
4 — FA50 (TB Output)
5 — FA51 (Analog Output)
P9 ASD Installation and Operation Manual
Direct Access Number — F854
Parameter Type — Hardware Selectable
Factory Default — Option-Specific
Changeable During Run — No
Minimum — 0
Maximum — 255
Direct Access Number — F870
Parameter Type — Selection List
Factory Default — None
Changeable During Run — Yes
Direct Access Number — F871
Parameter Type — Selection List
Factory Default — None
Changeable During Run — Yes
F871
227