FLC — FLC is the common leg of a single-pole double-throw form C relay. The FL relay is the Fault
Relay by default, but may be programmed to any of the selections of
information on this terminal, see
Note:
The FLA, FLB, and FLC contacts are rated at 2A/120 VAC and 2A/30 VDC.
Figure 8. FLA, FLB, and FLC Switching Contacts Shown in the Normal Operating Condition.
Note: The relay is shown in the normal operating condition. During
a faulted condition, the relay connection is FLC-to-FLA.
Figure 9. Terminal Board.
CAUTION
J100
1 to 2 = Sink (*)
2 to 3 = Source
J101
(24V)
1 to 2 = Sys. Supplied (*)
2 to 3 = Ext. Supplied
SW301
V/I Switch (I*)
TB1
TB2
TB3
TB4
*
= Default Setting
See
Typical Connection Diagram on pg. 26
See the section titled
See the section titled
cable/terminal sizes and torque specifications when making Terminal Board connections.
24
F132
and
Figure 8 on pg
Sink Source
Ensure that the ground screw is securely in
place to prevent arcing, intermittent
operation, or system failure.
SW200
Half / Full Duplex (*) Switch
S4
RS485 4-Wire Communication
Terminal Descriptions on pg. 22
Cable/Terminal/Torque Specifications on pg. 281
Table 9 on pg.
24.
for more information on the Terminal Board.
for terminal descriptions.
for information on the proper
P9 ASD Installation and Operation Manual
255. For further