Toshiba vlp technology P9 ASD Installation & Operation Manual page 176

Hide thumbs Also See for vlp technology P9 ASD:
Table of Contents

Advertisement

F438
Time-Based Alternation Process Hold Mode Response Time
Program Virtual Linear Pump VLP Time-Based Alternation
During Time-Based Alternation operation, while running in the Process Hold
mode, this parameter sets the time that the system may operate within the
maximum or minimum VLP zones before turning the ASD on or off,
respectively.
Time-Based Alternation Direct Mode Response Time
Program Virtual Linear Pump VLP Time-Based Alternation
During Time-Based Alternation operation, while running in the Direct mode,
this parameter sets the time that the system may operate within the maximum or
minimum VLP zones before turning the ASD on or off, respectively.
Power Running Torque Limit 1
Program Torque Torque Limit Settings
This parameter determines the source of the control signal for the positive
torque limit setting.
If Setting is selected, the value set at
Torque Limit 1 input.
Settings:
1 — V/I
2 — RR
3 — RX
4 —
F441
(Setting)
Power Running Torque Limit 1 Level
Program Torque Torque Limit Settings
This parameter provides a value for the Power Running Torque Limit 1
setting if
F441
is selected at parameter F440.
This value provides the positive torque upper-limit for the 1 motor.
Regenerative Braking Torque Limit 1
Program  Torque Torque Limit Settings
This parameter determines the source of the Regenerative Torque Limit
control signal.
If Setting is selected, the value set at
Settings:
1 — V/I
2 — RR
3 — RX
4 —
F443
(Setting)
168
F441
is used as the Power Running
F443
is used for this parameter.
Direct Access Number — F438
Parameter Type — Numerical
Factory Default — 7.5
Changeable During Run — No
Minimum — 0.0
Maximum — 6553.5
Units — Seconds
Direct Access Number — F439
Parameter Type — Numerical
Factory Default — 1000
Changeable During Run — No
Minimum — 0
Maximum — 65535
Units — Seconds
Direct Access Number — F440
Parameter Type — Selection List
Factory Default
—F441
(Setting)
Changeable During Run — Yes
Direct Access Number — F441
Parameter Type — Numerical
Factory Default — 250.0 (Disabled)
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.0 (Disabled)
Units — %
Direct Access Number — F442
Parameter Type — Selection List
Factory Default —
F443
Setting
Changeable During Run — Yes
P9 ASD Installation and Operation Manual