F480
VLP External Device Delay Timer
Virtual Linear Pump External Device Delay Timer
During a properly configured VLP operation, this parameter establishes the
time that the VLP operating level must remain within the
or the
VLP Minimum Zone
auxiliary pump.
See
Figures 31
and
32
for more information on the
VLP Minimum
Zone.
Increasing Load
If the VLP operating level of the Lead Pump is within the
Zone, and the External Device Delay Timer times out, OUT1 will change
states and activate an auxiliary pump (Lag1).
Should the VLP operating level return to the
duration in excess of the External Device Delay Timer, OUT2 will change
states and activate the second auxiliary pump (Lag2).
Decreasing Load
If operating in the
VLP Minimum
times out while OUT2 is activated, OUT2 will change states and deactivate the
second auxiliary pump (Lag2).
Should the system return to the
the External Device Delay Timer, OUT1 will change states and deactivate the
auxiliary pump (Lag1).
Note:
Set the Sleep Timer Delay (F383) to two (2) times the VLP
External Device Delay Timer (if using the Sleep Timer function)
as not to place the primary ASD in the sleep mode with Lag1
and/or Lag2 running.
Note:
Set OUT1 and OUT2 to External Device 1 and 2, respectively,
as required.
Auxiliary Pump Activation Sequence
PUMP ID
IF @
Lead Pump
Max Zone
Lag1 Pump
Max Zone
Lag2 Pump
Max Zone
Lag2 Pump
Min Zone
Lag1 Pump
Min Zone
Lead Pump
Min Zone
176
to activate/deactivate the Sleep Timer (F382) or an
VLP Maximum Zone
VLP Maximum Zone
Zone, and the External Device Delay Timer
VLP Minimum Zone
for a duration in excess of
AND
THEN
Activate
Counter Time = 0
OUT1
Activate
Counter Time = 0
OUT2
Run
Counter Time = 0
Continuous
Deactivate
Counter Time = 0
OUT2
Deactivate
Counter Time = 0
OUT1
Counter Time = 0
Direct Access Number — F480
Parameter Type — Numerical
Factory Default — 5
Changeable During Run — Yes
VLP Maximum Zone
Minimum — 0.1
Maximum — 6553.5
and
Units — Seconds
VLP Maximum
for a
Note:
OR
Sleep if
enabled
P9 ASD Installation and Operation Manual
F480
The number of pumps used