F735
Panel Reset Lock Out
Program Special Operation Panel Parameters
This parameter is model-specific and has no function on the P9 ASD system.
Settings:
0 — Unlocked
1 — Locked
Command Mode/Frequency Mode Change Lock Out
Program Utilities Prohibition
This parameter is model-specific and has no function on the P9 ASD system.
Settings:
0 — Unlocked
1 — Locked
Lock Out All Keys
Program Utilities Prohibition
This parameter is model-specific and has no function on the P9 ASD system.
Settings:
0 — Unlocked
1 — Locked
Trace Selection
Program Utilities Trace
In conjunction with parameter
and store 4 ASD output waveform data points. The data may be read and stored
as a function of a trip (At Trip) or it may be initiated by the activation of a
discrete terminal activation (At Trigger).
Set a discrete input terminal to Trace Back Trigger Signal and activate the
terminal to initiate the At Trigger read/store function.
Table 10 on pg. 256
lists the items that may be selected for the data read/store
function along with the associated communication number for each selection.
The duration of the read/store cycle for the selected items is set at parameter
F741.
To acquire and store the data a communications device and a PC are required.
The P9 ASD supports the following communications protocols: RS485
(MODBUS-RTU) Toshiba Protocol, USB Toshiba Protocol, CC-Link, ProfiBus,
and DeviceNet (Refer to the manual of each protocol type for more
information).
Trace data may be viewed graphically via Program  Utilities  View Trace
Data.
Settings:
0 — None (Disabled)
1 — At Trip
2 — At Trigger
216
F741
– F745, this parameter is used to monitor
Direct Access Number — F735
Parameter Type — Selection List
Factory Default — Unlocked
Changeable During Run — Yes
Direct Access Number — F736
Parameter Type — Selection List
Factory Default — Locked
Changeable During Run — Yes
Direct Access Number — F737
Parameter Type — Selection List
Factory Default — Unlocked
Changeable During Run — Yes
Direct Access Number — F740
Parameter Type — Selection List
Factory Default — At Trip
Changeable During Run — Yes
P9 ASD Installation and Operation Manual