Start/Stop Levels - Watts AERCO Benchmark BMK5000 Operation And Service Manual

Platinum boilers with edge controller
Hide thumbs Also See for AERCO Benchmark BMK5000:
Table of Contents

Advertisement

Benchmark Platinum-Edge [ii]: Operation-Service Manual
SECTION 3 - START SEQUENCE

3.3 START/STOP LEVELS

The start and stop levels are the Air/Fuel Valve positions (% open) that start and stop the unit,
based on load. These levels are Factory preset as follows:
TABLE 3-1a: Start/Stop Levels – NATURAL GAS
BMK
BMK
750/
750/1000
1000
DF
Start
22%
24%
Level:
Stop
18%
18%
Level:
Ignition
35%
30%
Position
TABLE 3-1b: Start/Stop Levels – PROPANE GAS
BMK
BMK
750/1000
750/
1000
DF
Start
22%
24%
Level:
Stop
18%
18%
Level:
Ignition
35%
30%
Position
Normally, these settings do not require adjustment.
Note that the energy input of the boiler is not linearly related to the Air/Fuel Valve position.
OMM-0137_J •
12/20/2022
BMK
BMK
BMK
1500
2000
2500
20%
24%
24%
16%
18%
16%
29%
29%
29%
BMK
BMK
BMK
1500
2000
2500
20%
24%
26%
16%
18%
18%
29%
29%
29%
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
BMK
BMK
BMK
3000
4000
5000N
20%
27%
24%
14%
23%
18%
29%
45%
40%
BMK
BMK
BMK
4000
5000N
3000
22%
24%
24%
14%
18%
18%
29%
35%
35%
BMK
4000 &
BMK
BMK
5000
6000
5000N
DF
24%
24%
24%
18%
18%
18%
35%
35%
50%
BMK
BMK
5000
6000
24%
24%
18%
18%
35%
50%
Page 23 of 167