Air Eductor Air Pump Maintenance - Bmk5000 & 6000 - Watts AERCO Benchmark BMK5000 Operation And Service Manual

Platinum boilers with edge controller
Hide thumbs Also See for AERCO Benchmark BMK5000:
Table of Contents

Advertisement

Benchmark Platinum-Edge [ii]: Operation-Service Manual
SECTION 8 – MAINTENANCE
Lean O
Sensor Maintenance Instructions
2
4. Next, loosen and remove the O
15/16" open-end wrench.
5. Thoroughly inspect the O
clean the sensor with a fine emery cloth.
6. Reinstall the O
sensor and crush washer on the burner plate.
2
7. Reconnect the sensor lead wire.
8. Reinstall the shroud on the unit.
NOTE:
If the AERtrim technology system is functioning, it should be inspected at the same time as
O
sensor maintenance. For instructions see Section 9: AERtrim Operation in this guide.
2
8.4.1 Air Eductor Air Pump Maintenance – BMK5000 & 6000
Benchmark Platinum 5000 and 6000 units contain an Air Eductor assembly, mounted just inside
Sensor Cover on the unit's back panel, (see Figure 8-3b, above). It includes an air pump,
the O
2
which draws an air sample from the combustion chamber past the O
accuracy.
The air pump contains an air pump filter (P/N 87008) should be inspected-cleaned every 12
months and replaced every 24 months. It is included in all BMK5000 & 6000 24 Month
Maintenance Kits.
Air Pump Maintenance and Troubleshooting Instructions
1. Remove the Air Pump's plastic air filter cover and clean or replace the air filter (see Figure
8-4, below).
2. If the Air Eductor or the Air Pump is not operating properly, try the following troubleshooting
steps:
a) Check the connector to the Air Pump for corrosion or contamination, clean as
needed.
b) If the Air Pump is not running, check 120 VAC power to the Air Pump. If 120 VAC
power is OK, replace the Air Pump.
c) If the Air Pump is running, check current drawn in series with one power wire. If the
current is within the range of 0.1 to 0.6 amps, the Air Pump is operating properly.
d) Check the signal from current sensor. If it is within the range of 0.20 to 1.20 VDC,
there may be a connector problem or IGST board issue. Check all connectors and
wires first. Try swapping IGST board with known good board before ordering a new
one.
OMM-0137_J •
12/20/2022
sensor and crush washer from the burner plate using a
2
sensor. If eroded, the sensor should be replaced. Otherwise
2
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
Sensor, ensuring its
2
Page 103 of 167

Advertisement

Table of Contents
loading

Table of Contents