Ignition Switch Open During Ignition; Safety Pressure Relief Valve Test - Watts AERCO Benchmark BMK5000 Operation And Service Manual

Platinum boilers with edge controller
Hide thumbs Also See for AERCO Benchmark BMK5000:
Table of Contents

Advertisement

Benchmark Platinum-Edge [ii]: Operation-Service Manual
SECTION 5 – SAFETY DEVICE TESTING
Purge Switch Open During Purge Check Instructions
DIAL
Figure 5-11c: Air/Fuel Purge and Ignition Locations – BMK5000 & 6000

5.11 IGNITION SWITCH OPEN DURING IGNITION

The Ignition switch (and the Purge switch) is located on the Air/Fuel Valve. To check the
switch, proceed as follows:
Ignition Switch Open During Ignition Check Instructions
1. Set the Controller's Enable/Disable switch to Disable.
Main Menu →Diagnostics→ Manual Run and then put the unit in Manual
2. Go to
3. Set the valve position between 25% and 30% using the + (Plus) and – (Minus) controls.
4. Remove the Air/Fuel Valve cover (Figure 5-10, above) by rotating the cover
counterclockwise.
5. Remove one of the two wires (#169 or #170) from the Ignition switch (see Figure 5-11a –
5-11c, above).
6. Set the Controller's Enable/Disable switch to Enable to start the unit.
7. The unit should begin its start sequence and then shut down and display Ign Switch Open
During Ignition.
8. Replace the wire on the Ignition switch and press the CLEAR button. The unit should
restart.

5.12 SAFETY PRESSURE RELIEF VALVE TEST

Test the safety Pressure Relief Valve in accordance with ASME Boiler and Pressure Vessel
Code, Section VI.
OMM-0137_J •
12/20/2022
AIR IN
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
TO BLOWER
PURGE
POSITION
SWITCH
IGNITION
POSITION
SWITCH
Page 81 of 167
Mode.

Advertisement

Table of Contents
loading

Table of Contents