GF-127
OMM-0052_0E
6.
Up to 7 seconds will be allowed for ignition to be detected. The igniter relay will be
turned off one second after flame is detected.
7.
After 2 seconds of continuous flame, Flame Proven will be displayed and the flame
strength will be indicated. After 5 seconds, the current date and time will be displayed
in place of the flame strength.
8.
With the unit firing properly, it will be controlled by the temperature controller circuitry.
The boiler's VALVE POSITION will be continuously displayed on the front panel
bargraph.
Once the demand for heat has been satisfied, the Control Box will turn off the dual SSOV
gas valves. The blower relay will be deactivated and the Air/Fuel Valve will be closed.
Standby will be displayed.

3.10 START/STOP LEVELS

The start and stop levels are the Air/Fuel Valve positions (% open) that start and stop the
unit, based on load. These levels are Factory preset as follows:
Normally, these settings should not require adjustment.
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
PR2: 04/22/13
Benchmark 2.0LN Dual-Fuel Low NOx Boiler
Operation and Maintenance Manual
Figure 3-6: Air/Fuel Valve In Ignition Position
Start Level:
Stop Level:
CHAPTER 3: CONTROL PANEL OPERATION
Natural Gas
Propane
25%
25%
20%
21%
Page 39 of 158