Benchmark Platinum-Edge [ii]: Operation-Service Manual
SECTION 7 – BOILER SEQUENCING TECHNOLOGY
BST Outdoor Air Reset Setpoint Instructions
9. The SH Operating Mode screen now appears; choose Outdoor Air Temperature Reset.
10. The Space Heating Outdoor Reset screen appears. Specify the minimum and maximum
inside and outside temperatures that will be used to create the associated OATR curve that
trigger the unit to turn on and off, and in Warm Weather Shutdown specify the threshold
outside temperature above which the unit shuts down.
17. If the unit will communicate with the site's BAS (Building Automation System), the Select
BAS Mode screen appears. Choose the communication protocol it will use, or else press
Off.
18. Fill in the parameters to establish communications with BAS via the option you selected.
19. Once the setup has been configured, the EZ Setup Complete screen displays a summary
of the completed setup as verification that the setup is complete and saved.