Watts AERCO Benchmark BMK5000 Operation And Service Manual page 120

Platinum boilers with edge controller
Hide thumbs Also See for AERCO Benchmark BMK5000:
Table of Contents

Advertisement

Benchmark Platinum-Edge [ii]: Operation-Service Manual
SECTION 9 – AERTRIM OPERATION
BMK750 AERtrim Values
MENU ITEM
Settle Time
Trim Gain
Max Tries
18%
O
Target
2
30%
45%
(must be
between
60%
O
Upper &
2
80%
O
Lower)
2
100%
18%
O
Lower
2
Limit
30%
45%
(must be at
60%
least 1%
80%
lower than
O
Upper)
100%
2
18%
O
Upper
2
Limit
30%
45%
(must be at
60%
least 1%
80%
higher than
O
Lower)
100%
2
O
Offset
2
BMK750 AERtrim Adjustment Range
CALIBRATION POINT
18%
30%
45%
60%
80%
100%
OMM-0137_J •
12/20/2022
Minimum
Maximum
0
120 Sec
0.1
5.0
0
100
3%
8%
3%
8%
3%
8%
3%
8%
3%
8%
3%
8%
2.5%
5.5%
2.5%
5.5%
2.5%
5.5%
2.5%
5.5%
2.5%
5.5%
2.5%
5.5%
5.5%
8.5%
5.5%
8.5%
5.5%
8.5%
5.5%
8.5%
5.5%
8.5%
5.5%
8.5%
-3.0
3.0
BLOWER VOLTAGE
Minimum
Maximum
1.75
2.85
1.95
2.60
2.35
3.60
3.00
3.90
3.80
4.75
4.75
6.00
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
Default
20 Sec
0.250
15
5.5%
5.5%
5.5%
5.5%
5.5%
5.0%
4.5%
4.5%
4.5%
5.0%
5.0%
4.5%
6.5%
6.5%
6.5%
6.0%
6.0%
5.5%
1.0
Default
2.10
2.55
3.10
3.50
4.60
5.60
Page 120 of 167

Advertisement

Table of Contents
loading

Table of Contents