SECTION 3 - START SEQUENCE

3.3 START/STOP LEVELS

The start and stop levels are the Air/Fuel Valve positions (% open) that start and stop the unit,
based on load. These levels are Factory preset as follows:
TABLE 3-1a: Start/Stop Levels – NATURAL GAS
BMK 750
Start Level:
22%
Stop Level:
18%
TABLE 3-1b: Start/Stop Levels – PROPANE GAS
BMK 750
Start Level:
22%
Stop Level:
18%
Normally, these settings do not require adjustment.
Note that the energy input of the boiler is not linearly related to the Air/Fuel Valve position.
OMM-115_D
GF-200
5/9/2019
BMK 1000
BMK 1500
22%
24%
18%
16%
BMK 1000
BMK 1500
22%
24%
18%
18%
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
126
BMK 2000
BMK 2500
24%
24%
18%
16%
BMK 2000
BMK 2500
24%
26%
18%
18%
BMK 3000
20%
14%
BMK 3000
22%
14%