SECTION 9 – AERTRIM OPERATION
BMK2000 AERtrim Values
MENU ITEM
Settle Time
Trim Gain
Max Tries
18%
O
Target
2
30%
40%
(must be
between O
50%
2
Upper & O
2
70%
Lower)
100%
18%
O
Lower
2
30%
40%
(must be at
least 1%
50%
lower than
70%
O
Upper)
2
100%
18%
O
Upper
2
30%
40%
(must be at
least 1%
50%
higher than
70%
O
Lower)
2
100%
O
Offset
2
BMK2000 AERtrim Adjustment Range
CALIBRATION POINT
18%
30%
40%
50%
70%
100%
OMM-0137_J •
12/20/2022
Minimum
Maximum
0
120 Sec
0.1
5.0
0
100
3%
8%
3%
8%
3%
8%
3%
8%
3%
8%
3%
8%
2.5%
5.5%
2.5%
5.5%
2.5%
5.5%
2.5%
5.5%
2.5%
5.5%
2.5%
5.5%
5.5%
8.5%
5.5%
8.5%
5.5%
8.5%
5.5%
8.5%
5.5%
8.5%
5.5%
8.5%
-3.0
3.0
BLOWER VOLTAGE
Minimum
Maximum
1.90
4.00
2.70
7.70
3.00
7.70
3.30
7.70
4.00
9.60
6.00
10.00
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
Default
20 Sec
0.250
15
6.5%
6.0%
6.0%
5.5%
5.5%
5.0%
5.0%
5.5%
5.5%
5.0%
5.0%
4.5%
7.0%
6.5%
6.5%
6.0%
6.0%
5.5%
1.0
Default
1.40
3.80
4.30
5.40
6.40
9.50
Page 123 of 167